Thursday, February 29, 2024

CFPS Exam Question Example -operating principles can be used in a gas-sensing fire detector

 

 

CFPS Exam Question Example 

 Which operating principles can be used in a gas-sensing fire detector or a combination (multisensor) detector ?

A)      Semiconductor, catalytic element, or infrared absorption.

B)      Spot type, beam type, or air sampling type.

C)      Heat type, ionization type, or dual-sensor type.

D)      Optical type, thermal type, or particle type.


 

Answer: A) Semiconductor, catalytic element, or infrared absorption.


Section 14 

CHAPTER 2 Automatic Fire Detectors 14-23


GAS-SENSING FIRE DETECTORS

Many changes occur in the gas content of the environment during a fire. It has been observed that detectable levels of gases are reached after detectable smoke levels and before detectable heat levels. One of three operating principles, that is, semiconductor, catalytic element, or infrared absorption, may be used in a gas-sensing fire detector or in a combination (multisensor) detector.

 

CFPS Exam Question Example : Which types of detectors are used to sense radiant energy emitted from combustion reactions?


CFPS Exam Question Example 

    Which types of detectors are used to sense radiant energy emitted from combustion reactions?

 

A)      Flame detectors and spark/ember detectors

B)      Smoke detectors and heat detectors

C)      Carbon monoxide detectors and gas detectors

D)      Motion detectors and occupancy sensors

 

Answer: A) Flame detectors and spark/ember detectors


----------------

Section 14

CHAPTER 2 Automatic Fire Detectors 14-23

RADIANT ENERGY–SENSING FIRE DETECTORS.

Radiant energy–sensing devices sense the radiant energy (electromagnetic radiation) emitted as a by-product of the combustion reaction, which obeys the laws of optics. This includes radiation in the ultraviolet, visible, and infrared portions of the spectrum, emitted by flames or glowing embers. They are categorized as flame detectors and spark/ember detectors.




CFPS Exam Example question - Which of the following statements is true about UV detectors used for fire detection?

 

CFPS Exam Question Example 

Which of the following statements is true about UV detectors used for fire detection?

A) UV detectors are not sensitive to hydrocarbons or metals.

B)  UV detectors are sensitive to all types of fires except hydrocarbons.

C) UV detectors are sensitive to most fires, including hydrocarbons, ammonia, sulfur, hydrogen, hydrazine, and metals

D) UV detectors are not effective in detecting fires caused by middle and heavy fraction petroleum distillates.


Answer: c) UV detectors are sensitive to most fires, including hydrocarbons, ammonia, sulfur, hydrogen, hydrazine, and metals.


SECTION 14 

14-24 SECTION 14 Detection and Alarm

Flame Detectors.

Ultraviolet Flame Detectors. 

The ultraviolet spectrum comprises wavelengths ranging from approximately 0.1µm to 0.35µm.  UV detectors typically use a vacuum photodiode Geiger-Muller tube to detect the ultraviolet radiation that is produced by a flame. The photodiode allows a burst of current to flow for each UV photon that hits the active area of the tube. When the number of current bursts per unit time reaches a set level, the detector initiates an alarm. A special control unit is required to monitor the count rates from UV detectors and initiate alarm.

UV detectors are sensitive to most fires, including hydrocarbons (liquids, gases, and solids), ammonia, sulfur, hydrogen, hydrazine, and metals such as magnesium. However, the smoke produced by combustion of middle and heavy fraction petroleum distillates is highly absorptive in the UV end of the spectrum, and this must be compensated for in system design if UV detectors are used


 

Wednesday, February 28, 2024

جدار الحريق فى الاسقف المائلة

جدران الحريق فى الاسقف المائلة

لضمان تحقيق الهدف من جدران الحريق يجب تحقيق بعض الشروط فى الاسقف المائلة مع بعض المتطلبات.










المتطلبات :

عندما تكون السقف من جهة واحدة أو كلا الجهتين لجدار الحريق مائلة نحو الجدار الحريق بميل يتجاوز 2 وحدة عمودية في 12 وحدة أفقية (2:12)، فيجب تحقيق بعض المتطلبات و هى تمديد جدار الحريق.


تمديد جدار الحريق بالطريقة التالية :

قياس ارتفاع السقف الموجود على بعد 1200 مم (1.2 متر) من جدار الحريق. إضافة 750 مم (0.75 متر) إلى هذا الارتفاع. يجب أن يمتد جدار الحريق إلى هذا الارتفاع المحسوب. ومع ذلك، إذا أسفر هذا الحساب عن ارتفاع أقل من 750 مم، فإن جدار الحريق يجب أن يمتد على الأقل إلى ارتفاع 750 مم.


    المرجع:
    1- الكود السعودى 201 : 706.6.2 Buildings with sloped roofs




Requirements for Fire Wall Extension in Buildings with Sloped Roofs


Introduction

Fire Wall Extension in Buildings with Sloped Roofs.






Requirement :

When the roof on one side or both sides of the fire wall slopes towards the fire wall at a slope greater than 2 units vertical in 12 units horizontal (2:12), certain requirements need to be met.

Extension of the Fire Wall

The fire wall needs to extend to a certain height to effectively contain a potential fire. This height is calculated as follows:
  1.    Measure the height of the roof located (4 ft.) 1200 mm (1.2 meters) from the fire wall.
  2.   Add (30 in.)750 mm (0.75 meters) to this height.
  3.  The fire wall should extend to this calculated height.
  4.  However, if this calculation results in a height less than (30 in.)750 mm, then the fire wall should still extend to a minimum height of (30 in.) 750 mm.

In essence, the regulation ensures that the fire wall extends to a sufficient height to properly contain any fire that might occur in buildings with sloped roofs, based on the slope of the roof and its proximity to the fire wall.

Reference :
SBC 201-2018: 706.6.2 Buildings with sloped roofs

Wednesday, May 3, 2023

FIRE PUMP CAPACITY AND HEAD RATING

 

The capacity and pressure ratings of fire pumps must be adequate to meet flow and pressure demands consistent with water supply requirements for the property in question. Fire pumps are designed to provide their rated capacity with a safety factor built in (150 percent of rated capacity at 65 percent of rated pressure) to provide some protection in case of greater than-expected demand at the time of a fire.





STANDARD HEAD DISCHARGE CURVES

The shape of the standard head discharge curve of a fire pump is determined by three limiting points: the shutoff, the rating, and the overload.



Shutoff

With the pump operating at rated speed and no flow, the total head of a horizontal centrifugal pump, vertical turbine pump, or an end-suction pump at shutoff must be between 100 and 140 percent of the rated head pressure at the 100 percent flow capacity.
The shutoff point represents the maximum allowable total head pressure. Otherwise, the pump would have a rising or convex characteristic curve. Such pumps are not listed. With a convex curve, there could be two flow points for one pressure.


Rating

The curve should pass through or above the point of rated capacity and head.
 

Overload

At 150 percent of rated flow capacity, the total head pressure should not be less than 65 percent of the rated total head. The curve should pass through or above the overload point. Most fire pumps have curves with a small margin above the theoretical overload, and some models have a cavitation or “break” point in the curve just beyond overload.



Source : NFPA 20

what the benefit of relief valve in fire pump ?

 

relief valve

These are required on the pump discharge line when the operation of the pump can result in excess pressure that would exceed the pressure rating of the fire protection system. The design of this device is very critical to the proper operation of the fire protection water supply. If the pump is oversized for flow and pressure, the main relief valve should not be used to limit the pressure and discharge excess quantities of water during the normal weekly run test and annual flow test. This is of particular importance in climates where there is freezing weather for a portion of the year. In these situations the designer should look further at other pump choices and optional drivers for the pump that will limit the discharge head. A good example is a variable-speed diesel engine or electric motor listed system.




NFPA 72 Understanding Supervisory Signal–Initiating Devices: Simplified Guide with Key Requirements"

Supervisory Signal–Initiating Devices Supervisory Signal–Initiating Devices This post explains the require...