Thursday, February 29, 2024

CFPS Exam Example question - Which of the following statements is true about UV detectors used for fire detection?

 

CFPS Exam Question Example 

Which of the following statements is true about UV detectors used for fire detection?

A) UV detectors are not sensitive to hydrocarbons or metals.

B)  UV detectors are sensitive to all types of fires except hydrocarbons.

C) UV detectors are sensitive to most fires, including hydrocarbons, ammonia, sulfur, hydrogen, hydrazine, and metals

D) UV detectors are not effective in detecting fires caused by middle and heavy fraction petroleum distillates.


Answer: c) UV detectors are sensitive to most fires, including hydrocarbons, ammonia, sulfur, hydrogen, hydrazine, and metals.


SECTION 14 

14-24 SECTION 14 Detection and Alarm

Flame Detectors.

Ultraviolet Flame Detectors. 

The ultraviolet spectrum comprises wavelengths ranging from approximately 0.1µm to 0.35µm.  UV detectors typically use a vacuum photodiode Geiger-Muller tube to detect the ultraviolet radiation that is produced by a flame. The photodiode allows a burst of current to flow for each UV photon that hits the active area of the tube. When the number of current bursts per unit time reaches a set level, the detector initiates an alarm. A special control unit is required to monitor the count rates from UV detectors and initiate alarm.

UV detectors are sensitive to most fires, including hydrocarbons (liquids, gases, and solids), ammonia, sulfur, hydrogen, hydrazine, and metals such as magnesium. However, the smoke produced by combustion of middle and heavy fraction petroleum distillates is highly absorptive in the UV end of the spectrum, and this must be compensated for in system design if UV detectors are used


 

Wednesday, February 28, 2024

جدار الحريق فى الاسقف المائلة

جدران الحريق فى الاسقف المائلة

لضمان تحقيق الهدف من جدران الحريق يجب تحقيق بعض الشروط فى الاسقف المائلة مع بعض المتطلبات.










المتطلبات :

عندما تكون السقف من جهة واحدة أو كلا الجهتين لجدار الحريق مائلة نحو الجدار الحريق بميل يتجاوز 2 وحدة عمودية في 12 وحدة أفقية (2:12)، فيجب تحقيق بعض المتطلبات و هى تمديد جدار الحريق.


تمديد جدار الحريق بالطريقة التالية :

قياس ارتفاع السقف الموجود على بعد 1200 مم (1.2 متر) من جدار الحريق. إضافة 750 مم (0.75 متر) إلى هذا الارتفاع. يجب أن يمتد جدار الحريق إلى هذا الارتفاع المحسوب. ومع ذلك، إذا أسفر هذا الحساب عن ارتفاع أقل من 750 مم، فإن جدار الحريق يجب أن يمتد على الأقل إلى ارتفاع 750 مم.


    المرجع:
    1- الكود السعودى 201 : 706.6.2 Buildings with sloped roofs




Requirements for Fire Wall Extension in Buildings with Sloped Roofs


Introduction

Fire Wall Extension in Buildings with Sloped Roofs.






Requirement :

When the roof on one side or both sides of the fire wall slopes towards the fire wall at a slope greater than 2 units vertical in 12 units horizontal (2:12), certain requirements need to be met.

Extension of the Fire Wall

The fire wall needs to extend to a certain height to effectively contain a potential fire. This height is calculated as follows:
  1.    Measure the height of the roof located (4 ft.) 1200 mm (1.2 meters) from the fire wall.
  2.   Add (30 in.)750 mm (0.75 meters) to this height.
  3.  The fire wall should extend to this calculated height.
  4.  However, if this calculation results in a height less than (30 in.)750 mm, then the fire wall should still extend to a minimum height of (30 in.) 750 mm.

In essence, the regulation ensures that the fire wall extends to a sufficient height to properly contain any fire that might occur in buildings with sloped roofs, based on the slope of the roof and its proximity to the fire wall.

Reference :
SBC 201-2018: 706.6.2 Buildings with sloped roofs

Wednesday, May 3, 2023

FIRE PUMP CAPACITY AND HEAD RATING

 

The capacity and pressure ratings of fire pumps must be adequate to meet flow and pressure demands consistent with water supply requirements for the property in question. Fire pumps are designed to provide their rated capacity with a safety factor built in (150 percent of rated capacity at 65 percent of rated pressure) to provide some protection in case of greater than-expected demand at the time of a fire.





STANDARD HEAD DISCHARGE CURVES

The shape of the standard head discharge curve of a fire pump is determined by three limiting points: the shutoff, the rating, and the overload.



Shutoff

With the pump operating at rated speed and no flow, the total head of a horizontal centrifugal pump, vertical turbine pump, or an end-suction pump at shutoff must be between 100 and 140 percent of the rated head pressure at the 100 percent flow capacity.
The shutoff point represents the maximum allowable total head pressure. Otherwise, the pump would have a rising or convex characteristic curve. Such pumps are not listed. With a convex curve, there could be two flow points for one pressure.


Rating

The curve should pass through or above the point of rated capacity and head.
 

Overload

At 150 percent of rated flow capacity, the total head pressure should not be less than 65 percent of the rated total head. The curve should pass through or above the overload point. Most fire pumps have curves with a small margin above the theoretical overload, and some models have a cavitation or “break” point in the curve just beyond overload.



Source : NFPA 20

what the benefit of relief valve in fire pump ?

 

relief valve

These are required on the pump discharge line when the operation of the pump can result in excess pressure that would exceed the pressure rating of the fire protection system. The design of this device is very critical to the proper operation of the fire protection water supply. If the pump is oversized for flow and pressure, the main relief valve should not be used to limit the pressure and discharge excess quantities of water during the normal weekly run test and annual flow test. This is of particular importance in climates where there is freezing weather for a portion of the year. In these situations the designer should look further at other pump choices and optional drivers for the pump that will limit the discharge head. A good example is a variable-speed diesel engine or electric motor listed system.




Sunday, April 30, 2023

Fire alarm Detector Placement

 

Spot-type detectors are usually installed on the ceiling, not less than 4 in. (0.1 m) from the wall. If their listing permits, they are also permitted to be installed on the wall, with their highest edge no less than 4 in. (0.1 m) and no more than 12 in. (0.3 m) from  the ceiling (Figure 14.2.16).





Where subject to mechanical damage, detectors must be protected. Any mechanical guard used with a smoke or heat detector must be listed for use with the detector. Otherwise, sensor performance may be degraded. Smoke detectors are often required to be set at higher sensitivity when used with plastic or perforated metal guards due to their effect on smoke entry. One manufacturer has a unique metal guard that looks like the series of smoke detectors it protects and that is engineered not to affect detector sensitivity. 

Smoke detectors should not be installed in an air stream from an HVAC supply grill, because that will inhibit smoke from a fire in the protected space from reaching the detector. (The smoke detector would be bathed in a clean air stream when the HVAC supply fan is running.) This can also affect heat detector performance, usually to a lesser degree. Locations adjacent to a return air grill should also be avoided, because returns can affect air circulation patterns in the room so as to inhibit the detection of smoke from low-energy fires.



FIRE ALARM SYSTEM BASICS

 

The basic components of each system are:

1. A system control unit (Figure 14.1.1) 




2. A primary, or main, power supply
3. A secondary, or standby, power supply
4. One or more initiating device circuits or signaling line circuits to which manual fire alarm boxes, sprinkler waterflow alarm initiating devices, automatic fire detectors, and other fire alarm initiating devices are connected
5. One or more fire alarm notification appliance circuits to which audible and visible fire alarm notification appliances, such as bells, horns, stroboscopic lamps, and speakers, are connected
6. Many systems also have an off-premises connection to a central station, proprietary supervising station, remote supervising station, or public fire service c
ommunication center by means of an auxiliary fire alarm system

Primary and Secondary Power Supplies
 The primary power is usually supplied by a connection to utility-generated electric power. The  connection must be from a branch circuit dedicated to the fire alarm system. The circuit and connections must be mechanically protected. The circuit disconnecting means must have a red marking, be accessible only to authorized personnel, and be identified as “Fire Alarm Circuit Control.” Inside the fire alarm system control unit, a permanent legend must identify the location of the electrical panel board that contains the circuit disconnecting means.


Secondary power supply for a fire alarm system is required to automatically supply the energy to the system within 30 seconds whenever the primary power supply is not capable
of providing the minimum voltage required for proper system operation.

The size of the secondary supply usually is measured in the amount of time that the secondary supply will operate the system, followed by a prescribed time period for the system to operate in an alarm condition. Local (protected premises), central station, remote station, proprietary, and auxiliary systems must have 24 hours of standby power, followed by 5 minutes of alarm. Emergency voice/alarm communication systems must have 24 hours of standby power, followed by 2 hours of emergency operation. To allow calculation of the power required for 2-hour emergency operation, NFPA 72 specifies that the 2 hours of emergency operation are the equivalent of 15 minutes of operation under full load (i.e., with all input devices and output appliances operating).



Interior Exit Stairways And Ramps Enclosures Fire Resistance.

Interior Exit Stairways And Ramps Enclosures. Interior Exit Stairways And Ramps Enclosures . must be constructed as fire barriers according ...