Supervisory Signal–Initiating Devices
This post explains the requirements for supervisory signal–initiating devices used to monitor systems like valves, pressure, water levels, and temperature.
1. Control Valve Supervisory Signal–Initiating Device
- Purpose: Monitors the position of control valves.
- Signals:
- Off-normal signal: Triggered when the valve moves from its normal position.
- Restoration signal: Triggered when the valve returns to its normal position.
- Trigger Conditions: Off-normal signal is activated:
- Within 2 handwheel revolutions or
- Within 1/5 of the valve’s travel distance.
- Restrictions: Device must not interfere with valve operation, obstruct indicators, or prevent maintenance.
2. Pressure Supervisory Signal–Initiating Device
- Purpose: Monitors system pressure for deviations.
- Signals:
- Off-normal signal: Triggered when pressure increases or decreases.
- Restoration signal: Triggered when pressure returns to normal.
- Applications:
- Pressure Tank: Detects changes of ±10 psi (70 kPa).
- Dry Pipe Sprinkler System: Same as pressure tank.
- Steam Pressure: Detects low pressure before it falls below 110% of the required level.
- Other Sources: Must comply with local authority requirements.
3. Water Level Supervisory Signal–Initiating Device
- Purpose: Monitors water levels to ensure safe operation.
- Signals:
- Off-normal signal: Triggered when water level rises or falls outside limits.
- Restoration signal: Triggered when water level returns to normal.
- Applications:
- Pressure Tanks: Triggered by a ±3 in. (70 mm) change.
- Other Containers: Low water signal triggered by a drop of 12 in. (300 mm).
4. Water Temperature Supervisory Signal–Initiating Device
- Purpose: Monitors water temperature in freezing conditions.
- Signals:
- Off-normal signal: Triggered when water temperature drops to 40°F (4.4°C).
- Restoration signal: Triggered when water temperature rises above 40°F (4.4°C).
5. Room Temperature Supervisory Signal–Initiating Device
- Purpose: Monitors room temperature to prevent freezing.
- Signals:
- Off-normal signal: Triggered when room temperature drops to 40°F (4.4°C).
- Restoration signal: Triggered when room temperature rises above 40°F (4.4°C).